Ideal Sure Test 61-059 Arc Branch Circuit Tester

Mitchell Part Number: ILJ-MiT753

Availability: Typically In stock - Call if Urgent!

$189.95
Add Items to Cart Add to Cart

Quick Overview

The SureTest Arc 61-059 from Ideal tests for correct wiring, open ground, reverse polarity, open hot, open neutral, hot and ground reversed, and hot on neutral with neutral open. It is designed to detect nearly all common improper wiring conditions.

Be the first to review this product

Tests AFCIs and GFCI's for proper operation
Tests for shared neutrals
Verifies wiring configuration
Compact size fits comfortably in pocket


How It Operates:


1. Plug the tester into the receptacle under test.
2. Verify that the receptacle is properly wired. The two outside green lights should illuminate indicating the circuit is configured properly.
3. If an improper wiring condition is indicated via the wiring indicator lights, refer to the indicator map on the product label to identify the problem.


 

Specifications

GUIDE FOR TESTING AFCI PROTECTED CIRCUITS
06-19-2008
As of June 2008 (serial# 0822001 or higher), the IDEAL AFCI Circuit Tester’s firmware has been modified to increase the arcing signature used to test CAFCI protected branch circuits.
Proper Test Methodology when using the IDEAL AFCI Circuit Tester model 61-059 for Branch Circuits Protected by AFCIs:
1. At the panel, operate the test button on the AFCI breaker installed in the branch circuit.
a. If the AFCI breaker trips, reset the breaker to restore power.
b. If the AFCI breaker does not trip, verify proper installation of the breaker. If the installation is correct and the breaker still does not trip, replace the faulty breaker.
2. Then, check each outlet on the branch circuit for proper wiring configuration by using the LEDs on the 61-059 tester.
3. Go to the furthest outlet on the branch circuit from the panel and conduct an AFCI trip test with the tester.
a. If the breaker trips, then use the tester to check that each outlet on the branch circuit has been de-energized to confirm that the outlets are on the same AFCI branch circuit.
b. If the breaker doesn’t trip, then the branch circuit may have excessive line impedance (i.e. voltage drop) from undersized wiring, loose wire connections and/or faulty wiring devices. The SureTest® model 61-165 can be used to further identify the source of high impedance on the branch circuit.

Shipping Weight 3.0000
Manufacturer Ideal
MPN 61-059
Manufacturer Warranty 1 Year
Mitchell Catalog Number 9EMiT753, 8E61058, 7E61058
upc code 676637