OSHA General Requirements - 1926.950 (c)(2)(ii)
Hotstick Length Guidance From OSHA General Requirements - 1926.950 (c)(2)(ii) Conductor support tools, such as link sticks, strain carriers, and insulator cradles, may be used: Provided, That the clear insulation is at least as long as the insulator string or the minimum distance specified in Table V-1 for the operating voltage.
|
Table V-1 - ALTERNATING CURRENT MINIMUM DISTANCES
|
|
|
Voltage range (phase to phase) (kV)
|
Minimum working and clear hot stick distance
|
|
2.1 to 15
15.1 to 35 35.1 to 46 46.1 to 72.5 72.6 to 121 138 to 145 161 to 169 230 to 242 345 to 362 500 to 552 700 to 765 |
2 ft. 0 in.
2 ft. 4 in. 2 ft. 6 in. 3 ft. 0 in. 3 ft. 4 in. 3 ft. 6 in. 3 ft. 8 in. 5 ft. 0 in. (1) 7 ft. 0 in.
(1) 11 ft. 0 in. (1) 15 ft. 0 in. |
|
Footnote (1) NOTE: For 345-362 kv., 500-552 kv., and 700-765 kv., minimum clear hot stick distance may be reduced provided that such distances are not less than the shortest distance between the energized part & the grounded surface.