AC Voltage Detector Distributor - Mitchell Instrument Company - call toll free: (888) 270 2690

Skip to Main Content »

Search Site
Welcome! Have Questions? Call us at: (888) 270 2690

ElControl Energy Explorer Three Phase Power Monitor/Analyzer/Datalogger

Double click on above image to view full picture

Zoom Out
Zoom In

More Views

  • ElControl Energy Explorer Three Phase Power Monitor/Analyzer/Datalogger
  • ElControl Energy Explorer Three Phase Power Monitor/Analyzer/Datalogger
  • ElControl Energy Explorer Three Phase Power Monitor/Analyzer/Datalogger
  • ElControl Energy Explorer Three Phase Power Monitor/Analyzer/Datalogger
  • ElControl Energy Explorer Three Phase Power Monitor/Analyzer/Datalogger
  • ElControl Energy Explorer Three Phase Power Monitor/Analyzer/Datalogger

ElControl Energy Explorer Three Phase Power Monitor/Analyzer/Datalogger

Mitchell Part Number: ELC-4BDCFC

Availability: Typically In stock - Call if Urgent!

$3,695.00
Add Items to Cart Add to Cart

Quick Overview

ElControl Energy Explorer 3-Phase Power Monitor/Analyzer/Datalogger Kit with 1000 Amp flex probes

Be the first to review this product

ElControl Energy Explorer Three Phase Power Monitor/Analyzer/Datalogger


 


ENERGY EXPLORER is an advanced Power Analyser, designed for use by electricians, plant engineers and energy professionals.
ENERGY EXPLORER provides fast and accurate measurement of all standard parameters characterizing the power consumption of electrical loads, such as the TrueRMS values of Voltage, Current, Frequency, Powers, Power Factor/CosPhi, Energy. ENERGY EXPLORER extends the analysis also to transient conditions of the load, thanks to the built-in Inrush Current function allowing voltage and current monitoring with pre-triggering.
The load’s consumption can be kept under close control thanks to the availability of fully configurable Average and Maximum Demand functions, user-settable alarms and configurable tariff-band energy analysis.
Historical, graphic trend-displays provide immediate understanding of how parameters change during a settable time frame.
In addition to the above, ENERGY EXPLORER provides also state-of-the-art analysis of dangerous and hidden phenomena such as Harmonics, Microinterruptions, Voltage Unbalance. The analysis of such phenomena is nowadays an indispensable troubleshooting tool, helping to minimize downtimes and malfunctions of increasingly complex electrical systems.

 


MAIN FEATURES


RMS METER:

3-Phase TRMS measurements of all electrical parameters characterizing the load's supply and power consumption, such as: Voltages, Currents, Powers, Energies, Frequency, Power Factor, CosPhi, Crest Factor, THD-V, THD-I, etc.
RMS Measures can be displayed as instantaneous, Min/Max or Average values with configurable integration time and mode:
-Fixed: fixed integration time-frame; the Average and MD values are  updated at the end of  each  fixed time-frame.
-Sliding: sliding integration time-frame; the Average and MD values are constantly updated  on the basis   of a sliding time-frame.
-Synchro: synchronized time-frame; the time-frame is synchronized by external control-signals, such as     provided by the energy utilities

SCOPE:

Real-Time display of the measured voltages' and currents' waveforms, their instantaneous RMS values and Phase-Angles.


HARMO:

Fully IEC61000-4-7 compliant measurement of voltage and current harmonics up to the 31st order.
The harmonics' data is displayed both graphically, as bar-graphs, and numerically. Each harmonic order is displayed as absolute value and percentage of the fundamental and includes the displacement angles between the harmonic voltage and currents, providing the power of the examined harmonic orde

TARIF-BAND MANAGEMENT:

Allows the configuration of up to 4 Tarif Bands with accounting of kWh, kVAh, cost and necessary reactive energy for PF correction.

PHASE VECTOR DISPLAY:

The Phase-Vector diagram provides a clear and immediate representation of the 3-Phase system's voltages, currents and phase angles, as well as the system's unbalance.

INRUSH/ START-UPCURRENTE CAPTURE:

Fully IEC61000-4-30 compliant capture and display of transient current events with pre-triggering functions. This function provides fast and reliable analysis of the start-up of motors / loads, connection of capacitor banks, etc.

ALARM FUNCTIONS:

Energy Explorer provides the possibility to set configurable alarm thresholds on any measured value, for immediate display and logging of the alarm conditions. Additionally, Energy Explorer is equipped with 2 Relay Outputs that can be linked to any of the set alarms or configured to become Pulse-Outputs.

MEASUREMENT SURVEYS/DATALOGGING:

Energy Explorer's extremely flexible memory system, based on extractable and exchangeable Compact Flash cards, allows to perform long and detailed measurement surveys. The surveys can be started/stopped at any time or scheduled to start and stop at a later time. Measurement surveys can be of two types:
-RMS: Surveys storing the RMS values of all measured parameters with a settable frequency.
-Waveform: Surveys storing the actual digital samples of voltages and currents with a settable frequency. When analysing such a survey on PC, not only the RMS values but also the actual waveforms of the signals will be available.

MAIN FEATURES:
Current & Voltage Measurement: Energy Explorer Kit includes a set of 3 flexible current probes with 5A-1000A measuring range and 41cm of length. Thanks to its special input circuit, Energy Explorer avoids the necessity of the usual external amplifier/integrator box for the flexible current probes. The elimination of the external circuit-box greatly improves the measurement accuracy, eliminates the short autonomy due to the amplifier's battery supply and enhances the natural ease-of-use of the flexible clamps.
For the voltage measurement Energy Explorer Kit includes a set of 6 measuring cables, color-coded and equipped with extractable crocodile clips.

Memory: Energy Explorer is already delivered with a massive 512Mb Compact Flash Card, allowing immediate use of Energy Explorer's survey capabilities.


PC Software: PE Studio,click here  a powerful and easy-to-use PC Software, specially designed to for the complete analysis and reporting of all data recorded by Energy Explorer, is included with Energy Explorer Kit.

Power Supply: Energy Explorer Kit comes with a desktop power supply (for the supply of the instrument and recharge of the batteries) and a set of 10 rechargeable, heavy-duty NiMh batteries (AA type, overall capacity 2300mAh).

Transport & Protection:
Special care was taken to ensure both high-protection and high-transportability for the Energy Explorer Kit. Energy Explorer is supplied with a shock- and water-proof IP67 plastic carrying case, resistant to corrosion and suitable for airplane transport. The above case is equipped with an internal, detachable soft-bag containing all the Energy Explorer Kit.

You may also be interested in the following product(s)

AEMC 3945-B PowerPad Power Quality Analyzer Kit - 240 Amp

AEMC 3945-B PowerPad Power Quality Analyzer Kit - 240 Amp
$3,695.00
     
Product Includes ElControl Energy Explorer Three Phase Power Monitor/Analyzer/Datalogger
Specifications

ElControl Energy Explorer Three Phase Power Monitor/Analyzer/Datalogger



--- INPUT SIGNAL SAMPLING ---
NUMBER OF INPUT CHANNELS    7
AD CONVERTER RESOLUTION    14 bits
SAMPLING SPEED:  22.4 kSamples/second at 50 Hz - 26.88 kSamples/second at 60 Hz

--- VOLTAGES ---       
NUMBER OF CHANNELS    3 with independent inputs
INPUT IMPEDANCE    3 MOhm
MAX VRMS BETWEEN CHANNELS    1000 VACRMS
MAX MEASURABLE Vpeak    1400 V
NUMBER OF SCALES    2
VRMS THAT CAN BE MEASURED
AT TERMINALS    1.5 ÷ 500   VACRMS low scale
                                     3 ÷ 1000 VACRMS high scale
PRECISION (RMS VALUES)    <±0.2% of the reading ± 0.05% of the full scale
PRECISION (peak VALUES)    <±5% of the reading ± 1% of the full scale

MAX VOLTAGE APPLICABLE
AT THE TERMINALS    600V CAT III pollution rating 2

--- CURRENTS ---
NUMBER OF CHANNELS    4 (3 + 1 auxiliary)
INPUT IMPEDANCE    10kOhm

MAX VOLTAGE APPLICABLE
AT THE TERMINALS:    5V peak-to-peak
TYPE OF CLAMPS THAT CAN BE USED:
     Flexible clamps without amplifier (except auxiliary channel)
    Traditional clamps (output 0 ÷ 1VAC)
     Flexible clamps with amplifier  (output 0 ÷ 1VAC)

CLAMP CONNECTOR    Type Hypertronics D01PB306NT
MEASURABLE IRMS  
    Flex clamps supplied 5 ÷ 1400ARMS
    Other clamps (output 0 ÷ 1VAC)
    0.3% ÷ 140% of the nominal current of the clamp used.

PRECISION (RMS VALUES)    <±0.2% of the reading ± 0.05% of the full scale + clamp error.
PRECISION (peak VALUES)    <±5% of the reading ± 1% of the full scale + clamp error

--- FREQUENCY ---                         
LIMIT VALUES FOR A COMPLETE ANALYSIS From 40 to 80 Hz (fundamental frequency)
PRECISION    ± 0.01 Hz

ENVIRONMENTAL
ALTITUDE    up to 3000m. The insulation category decreases above 3000m.
OPERATING TEMPERATURE    from 0° to 60° C
STORAGE TEMPERATURE    from -20 to 70°C
RELATIVE HUMIDITY  80% for temperatures up to 31°C with linear decrease up to 50% at the temperature of 40°C.


REFERENCE STANDARDS
SAFETY    EN 61010-1 Safety for electrical equipment for measurement
EMC           EN61326; EN61326/A1/A2/A3
                     Electromagnetic compatibility for electrical equipment for measurement.
MEASUREMENT
    EN 61004-30 Measurement methods.
    EN 61002-8 Measurement of losses of voltage and interruptions.
    EN 61004-7 Measurement of harmonics and interharmonics.
    EN 50160 Power quality.

ACCESSORY FEATURES
 
FLEXIBLE CLAMPS
OUTPUT VOLTAGE   39.1 µV/A at 50 Hz
INTERCHANGEABILITY ERROR   < 0.5%
LINEARITY  < 0.3%
ABSOLUTE ERROR  1%
DISPLACEMENT AT 50 Hz  <0.5°
PROTECTION RATING  IP65
SELF-EXTINGUISHING   UL94-V0
ELECTRICAL SAFETY  EN 61010-1 and EN 61010-2-32
                                             CAT III 1000VRMS–double insulation
LENGTH OF CONNECTION CABLE  200 cm
IDENTIFICATION   by purple, green and blue wire markers


VOLTAGE CONNECTION CABLES

COLOURS    red, yellow, blue
                        (the black plug identifies the neutral)
LENGTH       200 cm
INSULATION  CAT III 600V

POWER SUPPLY
INPUT VOLTAGE    100 ÷ 240 VAC
INPUT FREQUENCY    50-60Hz
OUTPUT VOLTAGE    12 VDC
POWER    40W


BATTERIES               
BATTERIES    10 rechargeable NiMh type AA 2300mAh batteries
BATTERY-OPERATION TIME about 2 hours with backlight ON >3 hours with backlight OFF
BATTERY CHARGER    Internal to the instrument
MAXIMUM BATTERY
RECHARGE DURATION
    about 20 hours, with instrument on
    about 10 hours, with instrument off


NOTE 1
The charge duration and lifetime of the batteries are influenced by the number and depth of the charge/discharge cycles carried out and by environmental factors such as, for example, temperature.

NOTE 2
To increase the battery operating time of  Energy Explorer, the screen backlight is switched off if no key is pressed for 3 minutes (press any key to switch it on again).

NOTE 3
The instrument turns off automatically if the batteries reach a voltage level below 5.9V, to prevent excessive battery discharge.

NOTE 4
If the instrument is not used for long periods (> 1 month), remove the batteries to preserve their charge/discharge capacity.


ELECTRICAL PARAMETERS MEASURED

VOLTAGE, CURRENT           
RMS values measured every 10/12 periods as per EN61000-4-30 standards, then                     aggregated to obtain a mean value per second.
NOTE: for measurement precision and range, see the «INPUT CHANNELS» specifications.

FREQUENCY    Frequency value of the three input voltage channels.
    Accuracy: ± 0.01 Hz
           
PF   
    Ratio between active and apparent power.
    Accuracy: ± 0.01 of full scale. 

ACTIVE POWER   
    Calculated as products between instant V and I.
    Accuracy: ±0.5% of the reading ± 0.1 of the full scale
REACTIVE POWER   
    Square root of apparent power and active power squares
    Accuracy: ±0.5% of the reading ± 0.1 of the full scale
 
APPARENT POWER   
    Calculated as product between the aggregate V and I on the second.
    Accuracy: ±0.5% of the reading ± 0.1 of the full scale

THD %:    MENU MEASURE

THD %:    MENU HARMONICS
              
HARMONICS    Harmonics from the 1 to the 31 order calculated by Fourier analysis carried out on 10/12 periods as per EN61000-4-7 standards.
Accuracy: ± input channel error ± n * 0.1%
COSø    Cosine of the angle between the voltage and the current vector of the harmonic component referred to the same phase. Angle accuracy U-I with traditional clamps 0-1V: ± n * 0.2° + clamp error
Angle accuracy U-I with flexible, non-amplified clamps: ± 1° ± n * 0.2° + clamp error
UNBALANCE:    Percentage of reverse sequence component of the voltage signal compared to the direct sequence component as per EN61000-4-30 standards.
   
ACTIVE ENERGY        Accuracy: ±0.5% of the reading ±0.1% of the full scale
REACTIVE ENERGY  Accuracy: ±0.5% of the reading ±0.1% of the full scale
APPARENT ENERGY   
    Accuracy:±0.5% of the reading ±0.1% of the full scale   
NOTE:      n  = harmonic order
                   N = number of samples
                   i  = instantaneous value
                   k =  analysis time
                   Ti = time interval (1 second)

 

PROTECTION RATING    IP20

KEYBOARD    Alphanumerical made of tactile rubber 

DISPLAY    5.7’’ 320x240 graphic colour LCD
    (115.2 X 86.4 mm)
    brightness: 200 cd/m2
    adjustable brightness/contrast.

MEASUREMENT REFRESH    1 second

OPERATING SYSTEM    LINUX

REAL TIME CLOCK  
   Month-day-year hour-minutes-seconds, can be set from the setup.
    Maximum error: ± 3 seconds per day at 25°C.
    Internal capacitor for data storage for the time required to replace the batteries.
    Video alarm when Energy Explorer is turned on in the event of data loss due to low batteries.

LANGUAGES    Italian, English, French, Spanish, German (settable from the setup).

CASE    Rigid IP67 case + internal case made of Cordura, dimensions 480 X 385 X 190 mm.

MEMORY
    Type I COMPACT FLASH up to 8 GB  (512 Mbytes supplied).
    Storage of values sampled by the AD converter (all input channels) or processed data (e.g. EN50160 reports).
With the supplied 512 Mbytes it is possible to store up to 9350 records, corresponding to 3 hours of uninterrupted campaign with a mains frequency of 50 Hz.
Each record includes the sample values of 60 periods on 7 channels.
Ex.: with a 8 GB memory, if 1 record every 5 minutes is selected, 240 days of storage are achieved; if 1 hour is selected, 8.5 years are achieved.

size 11.8" x 8.2" x 2.55"
Shipping Weight 15.0000
Power Supply rechargable battery pack
Manufacturer ElCotrol Energy
MPN Energy Explorer 4BDCFC
Manufacturer Warranty 1 Year